HSMS Linktest Timeout While Data Still Flows: Close the Socket Anyway
A swallowed Linktest.req burns T6 while an S1F1 on the same socket answers with a full S1F2 in 0.3 ms, and the host should close the connection anyway.
Industrial Knowledge Inventory
Practical notes for host and MES developers who need to understand SECS/GEM and HSMS before they have equipment to test against.
187 entries indexed · EN / KO · updated continuously
A swallowed Linktest.req burns T6 while an S1F1 on the same socket answers with a full S1F2 in 0.3 ms, and the host should close the connection anyway.
Core architecture, responsibilities, and vocabulary for HMI/SCADA projects.
Practical notes on Modbus, OPC UA, MQTT, SECS/GEM, and network troubleshooting.
Templates for naming, alarms, historian planning, commissioning, and field troubleshooting.
Debug without equipment
Explore SECS/GEM message exchanges in the shared browser demo, then compare them with a captured Select failure. It gives you a practical starting point before you have equipment to test against.
A public technical notebook: definitions, design notes, protocol reminders, checklists, and lessons learned from real industrial automation work. Clarity over marketing, useful references over generic content.